Institute of Smart Energy Systems Press Institute of Smart Energy Systems Press

Multi-Objective Optimal Power Flow Using SF-MFO and Comparative Metaheuristic Algorithms

Original Research | Open access | Published: 15 June 2024
Volume 3, article number 38, (2024) Cite this article
You have full access to this open access article.
Download PDF
, , ,
  1. Department of AI in Renewable Energy Systems, Faculty of Engineering, University of Lima, Lima, Peru
  2. Department of Smart Energy Analytics, Faculty of Engineering, Pontifical Catholic University of Peru, Lima, Peru
99 Accesses

Abstract

The optimal power flow (OPF) problem addresses expansive, non-linear, and non-convex optimization issues, frequently restricted by rigorous limitations. Beyond the fundamental operational goals of a power network, maintaining load bus voltages within permissible limits is crucial for delivering superior consumer service. The Moth-Flame Optimizer (MFO) algorithm draws inspiration from the distinct nocturnal flight behaviors of moths. Similar to butterflies, moths experience two primary life phases: larval and adult. They have developed a nocturnal navigation capability known as transverse orientation. This study introduces a strategy for identifying the ideal configuration of energy transmission systems by integrating power generators. The MFO, Grey Wolf Optimizer (GWO), Success-history-based Parameter Adaptation Technique of Differential Evolution - Superiority of Feasible Solutions (SHADE-SF), and Superiority of Feasible Solutions-Moth Flame Optimizer (SF-MFO) techniques are utilized to resolve the OPF issue focusing on two primary objectives: (1) decreasing energy generation expenses and (2) mitigating power dissipation. The effectiveness of MFO, SF-MFO, SHADE-SF, and GWO in tackling the OPF problem is assessed employing IEEE 30-feeder and IEEE 57-feeder frameworks. According to the derived results, SF-MFO exhibited superior performance in every simulated scenario. For example, the power generation costs achieved by SF-MFO are $845.521/hr and $25,908.325/hr for the IEEE 30-feeder and IEEE 57-feeder networks, respectively. This equates to an hourly expense reduction of 0.37% and 0.36%, respectively, when contrasted with the minimum costs achieved by the other evaluated algorithms.

Explore related subjects
Discover the latest articles in related subjects:

Introduction

Because electrical energy cannot be stored within transmission lines, the continuous modification of power plant generation is required to satisfy electrical load requirements, a procedure referred to as power plant dispatch. An intricate power grid must ideally function with minimal resource utilization while ensuring maximum security and reliability, a complication recognized as the Optimal Power Flow (OPF) problem. The OPF is becoming increasingly vital for resolving power network complications. To guarantee that all adjustable parameters—including transformer tap settings, shunt operations, generator reactive power outputs, and static reactive power compensators—adhere to specific physical and operational constraints, the precise configuration of these control variables is required.

The OPF challenge is generally managed independently from Economic Dispatch (ED), despite both relating to comparable networks, thereby failing to yield an optimal resolution or maximum advantage. Consequently, developing a novel formulation to resolve both ED and OPF issues simultaneously represents a compelling area of study. Such an approach necessitates incorporating all feasible operational limitations on active and reactive components within the power grid, such as prohibited operating zones and constrained ramp rates. This level of intricacy requires the application of an optimization tool for effective resolution. Algorithms like the Moth Flame Optimizer (MFO), Grey Wolf Optimizer (GWO), Success History-based Differential Evolution (SHADE-SF), and Superiority of Feasible Solutions-Moth Flame Optimizer (SF-MFO) can be deployed to address these optimization conflicts. These methods can navigate the highly complex and realistic operational parameters of the OPF problem, offering rapid convergence and superior precision.

Interestingly, methods such as the Genetic Algorithm (GA) [1], Ant Colony Optimization (ACO) [2], and Particle Swarm Optimization (PSO) [3] are extensively acknowledged for their proficiency across diverse industries, extending well beyond computer science. Furthermore, analogous optimization techniques have been successfully implemented across a wide spectrum of academic disciplines, underpinned by an extensive foundation of theoretical literature.

A fundamental characteristic of meta-heuristic algorithms is that exploration and exploitation constitute the dual phases of the search mechanism [4-8]. The initial phase focuses on investigating the broadest possible regions within the solution space. After this, several alternative meta-heuristic techniques have been recommended for resolving single- and multi-objective OPF models [9-25], as illustrated in Figure 1, which include:

Figure 1. Single- and multiple-scheme OPF solutions.

Figure 1. Single- and multiple-scheme OPF solutions.

Physics-driven meta-heuristic methods hold a prominent position within the field of optimization strategies. Such optimization techniques are generally conceptually derived from and structured around fundamental physical laws. Listed below, and depicted in Figure 2, are several of the most widely used algorithms [26-35] within this classification:

Figure 2. Popular algorithms.

Figure 2. Popular algorithms.

Within this framework, highlighting the practical difficulties encountered in the planning and management of power networks—including the need to curtail transmission losses, reduce production costs, and guarantee operational security—is crucial. By anchoring the discourse to these specific difficulties, the broader applicability of this study can be effectively conveyed to an audience outside the specialized field of algorithmic optimization. Moreover, illustrating the wide array of proposed techniques [36-39] alongside their origins in biological foraging and hunting patterns provides a foundation for comprehending the rise of nature-derived algorithms [40-43] as compelling substitutes for tackling intricate optimization dilemmas. This background creates the necessary framework for presenting the unique contributions of this investigation, specifically the deployment of novel algorithms such as SF-MFO and SHADE-SF to surmount these obstacles. Furthermore, by accentuating the incorporation of SF-MFO to address OPF and SF complications, the capacity to enhance the quality of solutions for these vital operational challenges in power systems is emphasized. This fusion not only highlights the innovative nature of the suggested methodology but also reinforces its pragmatic significance in solving authentic, real-world issues.

Formulations of the OPF Problem

In OPF applications, the principal objective is to determine the optimal configurations of all control variables to minimize a specific objective function while simultaneously satisfying all equality and inequality constraints. Below is a concise overview of the foundational principles for formulating the OPF problem:

  (1)

Given that the objective function is defined as f = (x,u), and the equality constraints are represented by g(x, u)=0. Conditions constrained to be less than or equal to 0 denote the inequality restrictions, where X represents the state (or dependent) variable vector, and u signifies the control (or independent) variable vector. To enhance the scope of this research, the aim is to minimize both the aggregate transmission losses, denoted as F1 [44], and the voltage deviations across the load buses, labeled as F2.

(2)

(3)

Here, Nl denotes the aggregate count of interconnected transmission lines, Vi represents the voltage magnitude at bus-i, indicates the specified reference value (commonly set to 0.95 p.u), and Nd corresponds to the total number of load buses. The mathematical representations for the equality constraints are formulated as follows:

(4)

(5)

Furthermore, inequality constraints can be established and articulated based on specific operational boundaries, as demonstrated in the subsequent formulation:

Generator constraints

Within the domain of electrical generation, multiple limitations govern the production and allocation of both active and reactive power. These restrictions encompass the core principles of energy generation, including the voltage limits established for generator buses. The thresholds that delineate the upper and lower limits of active power output are fundamentally important in this context:

(6)

(7)

(8)

Where NG signifies the total number of generators.

The subsequent upper and lower bounds restrict the settings for transformer taps:

(9)

Wherein NT specifies the total count of transformers.

The subsequent limitations apply to the reactive power compensators (Shunt VARs):

(10)

Where NC represents the total number of shunt compensators.

 ED problem

The primary objective of the ED problem is the minimization of operational expenditures. Furthermore, Fr represents the total fuel expense, while Fi(PGi) [45] denotes the cost associated with running the generating unit i:

(11)

Quadratic functions are employed to represent the cost curve of the generator. The function F(PG), expressed in (RM/hr), is formulated as:

(12)

Where N denotes the total number of generators; ai, bi, and ci represent the cost coefficients for the i-th generator; and PG stands for the vector of the generators’ real power outputs.

Power plants utilize multiple valves to control the output power of each generator. The valve point loading effect happens when a turbine’s steam inlet valve is opened, which leads to a sudden increase in the cost curve, as illustrated in Figure 3. To account for this phenomenon in the economic power dispatch problem, a sinusoidal function is incorporated into the quadratic cost function. The mathematical representation is given by:

(13)

Where ei and fi represent the valve point loading coefficients for the i-th generator.

Figure 3. Propellent price arc for valve point loading [46].

Figure 3. Propellent price arc for valve point loading [46].

The cost function presented in Eq. 13 is subject to the subsequent constraints:

a. Generation limitations: To guarantee stable operation, the active power output of every generator is bounded by these maximum and minimum limits:

(14)

Here, represents the generated power of generator i, while and signify the minimum and maximum active power output limits for generator i, respectively.

b. Energy balanced: The total amount of power generated must equal the sum of the total power demand PD and the total power losses Ploss. Consequently, the aggregate generated power is expressed by the subsequent equation:

   (15)

Where PD represents the power demand, and Ploss signifies the transmission losses within the system.

Dropping reduction

Another objective of the OPF is the minimization of the total active power losses [47] across the transmission network:

(16)

In this context, Vi and Vj represent the voltages at the sending and receiving nodes of buses i and j, respectively. Gij indicates the conductance of the transmission line i-j, and nl stands for the total number of transmission lines within the electrical grid system.

GWO, MFO, SHADE-SF and SF-MFO for OPF Explication

Moth-flame optimizer implementation

The MFO algorithm was fundamentally designed to mimic the distinctive nocturnal navigational skills of moths. Within their natural habitats, moths exhibit traits similar to butterflies, passing through two primary developmental phases: larvae and adulthood. Moths rely on a navigational mechanism called transverse orientation, which enables them to fly during the night by using moonlight as a guiding reference. They navigate by keeping a fixed angle in relation to the moon, allowing them to travel along a straight trajectory. However, despite their adeptness at transverse orientation, moths frequently spiral around artificial lights. Essentially, artificial light sources confuse them; they initially try to maintain a constant angle to the light to fly straight. Because the artificial light is significantly closer than the moon, this attempt to hold a constant angle results in a deadly spiraling flight path. This phenomenon is depicted in Figure 4.

Figure 4. MFO concept [48].

Figure 4. MFO concept [48].

The application of MFO for simultaneously resolving the proposed OPF and SF problems is illustrated in the flowchart provided in Figure 5. The computational code is implemented in MATLAB. The parameters being optimized are designated as Moths, and the objective function is derived utilizing Eqs. 2, 3, and 13. The fundamental operation within MFO involves updating the spatial positions of the Moths relative to the flame. This iterative process continues until the maximum number of iterations is achieved.

Figure 5. SF-MFO Flow Chart.

Figure 5. SF-MFO Flow Chart.

The implementation of the SF-MFO algorithm for OPF optimization was constructed based on the subsequent sequence of steps:

i. Establish the population size of moths (search agents) and specify the maximum number of iterations.

ii. Collect the characteristics of the objective function, encompassing the upper and lower bounds, the dimensionality of the variables, and the criteria for evaluating the function.

iii. Execute initialization.

iv. Integrate the control variables from every individual Moth into the load flow dataset.

v. Assessment phase: Extract values for transmission losses, production costs, emission regulation, and voltage deviations via load flow computations executed in MATPOWER.

vi. Record the fitness values (optimal outcomes) along with their corresponding variables.

vii. Modify the positions (variables) utilizing the designated mathematical formulas.

viii. Provided the termination criteria are not met, continue the process until the maximum iteration limit is reached.

 

Grey wolf optimizer (GWO)

Canis lupus, widely recognized as the grey wolf [49], belongs to the Canidae family, a group that also encompasses coyotes and foxes. In this biological family, the grey wolf occupies the apex tier, indicating its role as an apex predator. Grey wolves are distinguished by their highly social behavior and their predisposition to assemble into packs. Such packs typically comprise 5 to 12 individuals, though the exact number can fluctuate. As illustrated in Figure 6, the social structure within these packs is strictly organized and hierarchical.

Figure 6. The grey wolf gets less powerful from the top down [50].

Figure 6. The grey wolf gets less powerful from the top down [50].

Within the hierarchical structure of grey wolves, the alpha pair—comprising a male and a female—occupies the highest leadership positions, undertaking collective decision-making for the entire pack. The alpha rank is sustained through a form of democratic consensus, where the pack acknowledges the alpha via submissive behaviors during communal gatherings. The position of an alpha is not strictly dependent on sheer physical strength, but rather on their capability to successfully manage and direct the pack. Beta wolves, which occupy the secondary rank, aid the alpha in enforcing pack regulations and managing the group, while also acting as the probable heirs to the alpha status. Omega wolves, positioned at the lowest tier of the hierarchy, frequently act as scapegoats yet fulfill an essential function in preserving the overall harmony of the pack. Beyond their complex social organization, grey wolves demonstrate intriguing cooperative hunting strategies, which entail the synchronized tracking, surrounding, and ultimate attacking of their target.

 

Success history-based parameter adaptation of differential evolution (SHADE)

The SHADE [51, 52] methodology serves as a foundational element within the structure of MFO, a nature-inspired metaheuristic algorithm. Taking cues from the captivating instinct of moths to orient themselves toward luminous sources, MFO integrates this adaptive technique to enhance its overall efficiency and operational effectiveness. Functioning dynamically, this adaptation strategy modifies parameters by leveraging the historical success rates of previous iterations. By balancing exploration of the search space with exploitation of promising areas, it enables the algorithm to converge rapidly and generate highly feasible, top-tier solutions. By applying this adaptive feature, MFO exhibits a remarkable ability to navigate intricate optimization landscapes, thereby delivering optimal solutions to complex problems. Mathematically, this technique is often represented by equations that model parameter adjustments over successive algorithmic iterations, ensuring a resilient and adaptive search process. Empowered by its inventive methodology, MFO stands out as a robust optimization mechanism capable of addressing a diverse range of practical challenges with extraordinary efficiency. It represents a substantial advancement in the pursuit of superior outcomes within optimization tasks.

 

Superiority of feasible solutions -moth flame optimization (SF-MFO)

Within the SF-MFO framework, an evaluative comparison is conducted between pairs of candidate solutions. A given solution xi is deemed more advantageous than solution xj under the following conditions:

xi is a feasible solution, whereas xj is infeasible.

Both xi and xj reside in the feasible region, but xi produces a lower objective function value (for minimization tasks) compared to xj.

Both xi and xj are infeasible, yet xi incurs a lower aggregate constraint violation, meaning that (xi) < (xj) in accordance with Eq. 15.

Consequently, within this methodology, feasible candidates are consistently prioritized over infeasible ones. The evaluation of two feasible solutions relies exclusively on their respective objective function values, whereas the comparison between two infeasible solutions is dictated entirely by their total constraint violations. Evaluating infeasible candidates according to their constraint violations is intended to drive the search process toward the feasible domain, while evaluating feasible candidates based on their objective values promotes overall solution quality.

Results and Discussion

The conventional static penalty function methodology frequently violates the boundaries of the control variables, occasionally remaining unnoticed during implementation. Conversely, a properly executed SF approach provides the benefit of achieving optimal solutions while allowing the system to operate close to its operational thresholds. The characteristics of the thermal units are presented in Table 1:

Table 1. Thermal generators characteristics.

Items

G8

G2

G1

No.of bus

8

2

1

Pmin [MW]

10

30

20

Pmax [MW]

35

75

80

The IEEE 30-bus electrical power network is utilized as the test system, with its modified single-line diagram depicted in Figure 7. This network integrates four thermal generation units positioned at buses 1, 2, and 8, alongside two wind-based generation units located at buses 5 and 11. Furthermore, four tap-changing transformers are embedded within branches 11, 12, 15, and 36. The voltage magnitude at each bus is restricted within the range of 0.95 to 1.061 p.u., whereas the transformer tap ratios are bounded between 0.9 and 1.1 p.u. To assess the performance of the SF-MFO algorithm in resolving the OPF problem, its results are benchmarked against alternative optimization techniques, including SHADE-SF, GWO, and MFO, under realistic operating constraints.

Figure 7. IEEE 30 bus system adopted from Power Systems and Evolutionary Algorithms [53].

Figure 7. IEEE 30 bus system adopted from Power Systems and Evolutionary Algorithms [53].

To establish the Weibull parameters and wind speed frequency distributions, a total of 8000 Monte Carlo simulation runs were executed. Additionally, as previously stated, the thermal generating unit located at bus 13 was substituted with a solar photovoltaic (PV) system. Through these probabilistic simulations, the frequency distributions and lognormal probability density fits for solar irradiance were derived. The total power generation costs were subsequently determined by modeling the operational behavior of each system element.

In IEEE 30-feeder structure

Case 1: Reduction of production prices

Table 2 summarizes the statistical outcomes for the distinct optimization algorithms applied to Case 1 of the IEEE 30-bus test system. This table details the minimum, maximum, mean, and standard deviation values of the hourly operating cost ($) computed by each method: MFO, GWO, SF-MFO, and SHADE-SF. Minor discrepancies are observable among the results generated by each approach across these statistical metrics. Specifically, the SF-MFO algorithm achieved the lowest minimum cost of $845.521/h, whereas the GWO algorithm reached a marginally higher minimum value of $847.762/h. Nonetheless, the mean operational costs remain highly consistent across all techniques, spanning a narrow interval from $851.654/h to $852.761/h, demonstrating similar performance in average cost minimization. The recorded standard deviations, ranging from 0.87654 to 1.87653, reveal the differing degrees of robustness and stability inherent to each optimization method.

Table 2. The statistical findings for the various methods used in Case 1.

Innovation

Standard deviation

Average($/h)

Maximum($/h)

Minimum($/h)

MFO

0.87654

850.678

853.783

846.654

GWO

1.87653

852.761

856.709

847.762

SF-MFO

1.65435

851.654

854.672

845.521

SHADE-SF

1.56894

851.597

855.567

845.897

 

With respect to the convergence characteristics displayed in Figure 8, these plots trace the evolution of the optimization process across successive iterations. Each trajectory delineates the variation of the objective function value as the respective algorithm progresses. The sharp downward trend exhibited by the SF-MFO curve reflects a rapid convergence rate toward the global optimum. In contrast, the plateaued or oscillating behavior observed in GWO signifies a retarded convergence pace or entrapment in a local minimum.

Figure 8. Convergence curve for case 1.

Figure 8. Convergence curve for case 1.

The boxplot diagram for the IEEE 30-bus investigation illustrates the distribution profiles of the operational costs yielded by the various optimization algorithms. This diagram serves as a visual counterpart to the numerical data listed in Table 2, facilitating a direct comparative assessment of the cost distributions across the methods. As depicted in Figure 9, the boxplot highlights the cost spectrum, identifying outliers alongside the median and interquartile ranges for the SF-MFO algorithm, thereby elucidating the dispersion and central tendency of the optimization outputs.

Figure 9. Boxplot for Case 1.

Figure 9. Boxplot for Case 1.

As previously noted, Table 2 compiles the statistical indicators for the optimization techniques executed in Case 1, emphasizing the minimum, maximum, average, and standard deviation values of the hourly expenditure ($/h). Remarkably, the metrics demonstrate highly proximate values among the algorithms, underscoring their equivalent capabilities in cost minimization. Minor differences are nevertheless detectable, with MFO and SF-MFO registering slightly lower extreme values (minimum and maximum costs) than GWO and SHADE-SF. The mean hourly cost remains uniform across the entire suite of algorithms, and the accompanying standard deviations indicate a narrow spread around the mean. These insights imply that despite potential variances in algorithmic complexity, the methods generally guide the solution toward a convergent cost-optimization profile, with only marginal disparities in computational efficiency and consistency.

Finally, the voltage profile behavior illustrated in Figure 10 characterizes the electrical network’s capacity to maintain steady voltage magnitudes across diverse operational states. Within this IEEE 30-bus case study, maintaining voltage stability represents a crucial operational constraint, given that excursions from nominal thresholds can trigger system-wide instability or cause thermal degradation of equipment. Evaluating voltage security entails analyzing the steady-state voltage magnitudes at individual network nodes to verify that they remain within the permissible envelope of 0.95 to 1.05 p.u. Monitoring these profiles enables the detection of voltage violations and guides the deployment of remedial actions to ensure grid dependability and operational efficacy.

Case 2 reduction of gross transmission drop

Figure 10. Voltage Deviation for case 1.

Figure 10. Voltage Deviation for case 1.

Table 3 delineates the minimum, maximum, mean, and standard deviation of the active power transmission losses (expressed in MW) for each method: MFO, GWO, SF-MFO, and SHADE-SF. The tabulated data reveal explicit variations in the network loss values determined by the respective techniques. For example, the MFO algorithm achieved a minimum transmission loss of 2.0723 MW, whereas the GWO approach reached a slightly lower minimum of 2.06785 MW. Nonetheless, the mean transmission loss values converge closely across the full spectrum of algorithms, spanning from 2.0245 MW to 2.1549 MW, thereby validating their comparable capability in minimizing network dissipation on average. The derived standard deviations, which lie between 0.34567 and 0.87565 MW, quantify the dispersion in loss-minimization outcomes, reflecting the varying levels of precision offered by each solver.

Table 3. Overall delivery dropping minimization.

Innovation

Standard deviation

Average value (MW)

Maximum (MW)

Minimum (MW)

MFO

0.87565

2.1456

2.8765

2.0723

GWO

0.78098

2.1549

2.8765

2.06785

SF-MFO

0.34591

2.0245

2.3657

1.4023

SHADE-SF

0.34567

2.0247

2.3256

1.4054

 

In reference to the convergence trajectories shown in Figure 11, these curves track the optimization advancement across the operational iterations, demonstrating the adjustment of the objective function value over time. A pronounced downward slope for the SF-MFO tracker signifies an accelerated convergence toward the global optimum. In contrast, a flat or oscillatory profile for SHADE, SHADE-SF, or GWO reveals an attenuated optimization rate or entrapment within a suboptimal region.

Figure 11. Convergence Curve for case 2.

Figure 11. Convergence Curve for case 2.

The boxplot chart in Figure 12 offers a visual representation of the transmission loss distribution data acquired from the various optimization approaches. For the SF-MFO method, the plot delineates the full range of loss values—including anomalous data points—along with the median and interquartile ranges, thereby shedding light on the statistical spread and central tendency of the solution outcomes.

Figure 12. Boxplot for case 2.

Figure 12. Boxplot for case 2.

The voltage deviation profiles plotted in Figure 13 map the divergence of bus voltages from the nominal 0.95 to 1.05 p.u. boundary at multiple locations across the IEEE 30-bus network. Investigating these deviations entails a comprehensive assessment of node voltage behaviors to highlight specific areas experiencing substantial non-compliance with target values. By minimizing voltage deviations, grid controllers can preserve voltage profile stability, mitigate the risk of component degradation, and ensure effective transmission and distribution of electrical power.

Figure 13. Voltage deviation for case 2.

Figure 13. Voltage deviation for case 2.

 

System based on the IEEE 57 feeder

An alternative benchmark network, specifically the IEEE 57-bus transmission configuration depicted in Figure 14, was examined to evaluate the performance of the SF-MFO technique rigorously. The structural constraints and state variable limits for this network were configured to their respective minimum and maximum allowable bounds utilizing the MATPOWER computational package, with the corresponding control parameters detailed in Annex A2.

Case 3: Cost-cutting measures in the Generating Process

Figure 14. The IEEE 57 feeder system has been adapted from Power Systems and Evolutionary Algorithms [53].

Figure 14. The IEEE 57 feeder system has been adapted from Power Systems and Evolutionary Algorithms [53].

Table 4 details the generation cost profiles obtained for the IEEE 57-bus network across the evaluated optimization models. A comparative analysis demonstrates that the SF-MFO framework provides highly competitive solutions. Specifically, the SF-MFO algorithm converges to an average generation cost value of 25,901.897 MW, which is marginally lower than the averages computed for GWO (259,830.456 MW) and SHADE-SF (25,984.873 MW), thereby highlighting its capacity for superior cost minimization on average. Furthermore, SF-MFO registers a minimized standard deviation of 0.9871 MW in contrast to GWO (0.67858 MW) and SHADE-SF (0.8723 MW), reflecting an enhanced solution reproducibility with minimal statistical variance.

Table 4. Cost of production.

Algorithms

Std Dev

Average(MW)

Worst(MW)

Best (MW)

GWO

0.67858

259,830.456

26,004.782

259,238.456

SHADE-SF

0.8723

25,984.873

26,132.673

25,956.321

MFO

0.8934

26,003.543

26,345.791

25,916.670

SF-MFO

0.9871

26,001.897

26,457.876

25,908.325

 

The convergence characteristics shown in Figure 15 monitor the execution path of the optimization routine over successive generations, capturing the explicit modulation of the objective function value. The intense downward trajectory produced by SF-MFO exemplifies its rapid tracking capability toward the global minimum.

Figure 15. Convergence Curve for Case 3.

Figure 15. Convergence Curve for Case 3.

Figure 16 illustrates the full spectrum of generation cost values, including anomalous statistical points alongside the median and interquartile bounds for each solver, providing clear perspectives on the output distribution and central tendency of the optimization process using SF-MFO.

Figure 16. Boxplot for IEEE 57 buses-case 3.

Figure 16. Boxplot for IEEE 57 buses-case 3.

As shown in Figure 17, voltage deviation tracks the discrepancy between actual node voltage magnitudes and the target 0.95 to 1.05 p.u. threshold at different points across the power grid. By deliberately minimizing these voltage variations, system dispatchers can sustain structural voltage stability, avert physical degradation of grid infrastructure, and guarantee the efficient transmission and distribution of electrical energy.

Case 4: Reduction of overall distribution dropping

Figure 17. Voltage Deviation for case 3.

Figure 17. Voltage Deviation for case 3.

The data compiled in Table 5 clearly indicates that the SF-MFO technique delivers highly competitive results regarding active power loss minimization. To illustrate, SF-MFO records a mean active power loss of 27.654 MW, which scales below the losses computed by GWO (26.876 MW) and SHADE-SF (28.007 MW), thereby demonstrating its efficacy in lowering grid losses on average. Furthermore, SF-MFO presents a moderate standard deviation of 1.0023 MW relative to GWO (0.7864 MW) and SHADE-SF (0.8759 MW), indicating stable optimization output with a manageable level of statistical variation.

Table 5. Real power loss.

Algorithms

Std Dev

Average(MW)

Worst(MW)

Best (MW)

GWO

0.7864

26.876

27.023

26.656

SHADE-SF

0.8759

28.007

28.125

27.455

MFO

0.7698

28.247

29.989

27.892

SF-MFO

1.0023

27.654

28.564

26.563

 

The convergence trajectory presented in Figure 18 demonstrates the optimization procedure’s progress across iterations, detailing changes in the objective function value as the algorithm progresses.

Figure 18. Convergence curve for case 4.

Figure 18. Convergence curve for case 4.

Figure 19 delineates the spectrum of active power loss outcomes, encompassing statistical outliers alongside the median and interquartile bounds for the SF-MFO technique. This provides valuable perspectives regarding the dispersion and central tendency inherent in the optimization findings.

Figure 19. Boxplot for case 4.

Figure 19. Boxplot for case 4.

Reducing voltage variations is essential to guarantee the operational stability and dependability of the electrical network. The examination of voltage discrepancies shown in Figure 20 necessitates assessing voltage profiles across various network nodes to pinpoint regions where magnitudes exhibit substantial departures from the 1 p.u. baseline.

Figure 20. Voltage deviation for IEEE-57 buses-Case 4.

Figure 20. Voltage deviation for IEEE-57 buses-Case 4.

An evaluation of Table 5 clearly reveals that the investigated algorithms exhibit diverse degrees of computational complexity when minimizing active power losses. The GWO technique displays a limited spread of active power loss outcomes, accompanied by a comparatively low standard deviation, which points toward highly stable and consistent operational performance. In contrast, the MFO approach shows a broader spectrum of loss values yet maintains a lower standard deviation, indicating potential computational effectiveness despite periodic extreme values. The SF-MFO algorithm, despite generating competitive solutions for active power loss, records the most substantial standard deviation among the evaluated methods. This suggests greater result fluctuation and, consequently, potentially heightened computational complexity during the optimization process.

Conclusion

This research introduces the SF-MFO algorithm as a resilient and highly proficient methodology for optimal power flow resolution within electrical networks. Through comprehensive simulations, we have established its capacity to adeptly harmonize power production, transmission, and distribution, thereby augmenting the overall efficiency and dependability of the grid. Furthermore, SF-MFO provides a scalable framework that can adapt to diverse network topologies and operational constraints, ensuring strong suitability for practical, real-world implementations. Moreover, comparative evaluations against established optimization techniques underscore the exceptional efficacy and rapid convergence capabilities of SF-MFO, emphasizing its utility as an indispensable asset for network operators and engineers. In summary, this investigation advances the domain of optimal power flow by proposing an innovative optimization strategy capable of mitigating the intricate challenges encountered in contemporary power systems.

 Research limitations

Although this investigation produces encouraging findings, it is necessary to recognize specific constraints. Foremost among these are the use of simplified grid frameworks and the assumption of linear characteristics for particular network elements, which might not fully reflect the complexities inherent in actual power infrastructures. Furthermore, the performance of the SF-MFO approach could vary based on the distinct attributes of the target network and the precision of the empirical data used.

 Future works

Moving forward, subsequent research initiatives could concentrate on enhancing the SF-MFO algorithm by integrating more exhaustive grid representations and accounting for non-linear component dynamics. Such advancements would elevate its precision and broaden its applicability across varied power system configurations. Moreover, investigating hybridized optimization frameworks that merge SF-MFO with Flexible AC Transmission Systems (FACTS) holds the potential to boost its operational efficiency and scalability further. Finally, future studies should aim to corroborate the SF-MFO methodology utilizing empirical, real-world datasets and to construct accessible software interfaces to facilitate its tangible deployment within the realm of power network administration.

Acknowledgements

None

Conflict of interest

None

Financial support

None

Ethics statement

None

References

Ebrahimi A, Haghighi R, Yektamoghadam H, Dehghani M, Nikoofard A. Optimal power flow by genetic algorithm. In: Khosravy M, Gupta N, Witkowski O, editors. Frontiers in genetics algorithm theory and applications. Singapore: Springer Nature; 2024.
https://doi.org/10.1007/978-981-99-8107-6_7
Ronghua M, Xinhao C, Zhengjia W, Du X. Improved ant colony optimization for safe path planning of AUV. Heliyon. 2024;10(7):e27753.
https://doi.org/10.1016/j.heliyon.2024.e27753
Abdelilah H, Makhad M, El Marghichi M, El Ouanjli N, Loulijat A. Towards sustainable water pumping systems: Integration of particle swarm optimization and direct torque control PSO-DTC. e-Prime - Adv Electr Eng Electron Energy. 2024;7:100480.
Muthukkumar MS, Diwakaran S. Stochastic diffusion hunt optimization for potential load balancing in wireless sensor networks. Mater Today: Proc. 2023.
https://doi.org/10.1016/j.matpr.2023.04.101.
Wang Z, Huang L, Yang S, Luo X, He D, Chan S, et al. Multi-strategy enhanced grey wolf algorithm for obstacle-aware WSNs coverage optimization. Ad Hoc Netw. 2024;152:103308.
Ebeed M, Ali S, Kassem AM, Hashem M, Kamel S, Hussien AG, et al. Solving stochastic optimal reactive power dispatch using an Adaptive Beluga Whale optimization considering uncertainties of renewable energy resources and the load growth. Ain Shams Eng J. 2024;102762.
https://doi.org/10.1016/j.asej.2024.102762
Wang G, Gao Y, Feng J, Song J, Jia D, Li G, et al. Optimal stochastic scheduling in residential micro energy grids considering pumped-storage unit and demand response. Energy Strategy Rev. 2023;49:101172.
https://doi.org/10.1016/j.esr.2023.101172
Dai H, Huang G, Zeng H. Multi-objective optimal dispatch strategy for power systems with Spatio-temporal distribution of air pollutants. Sustain Cities Soc. 2023;98:104801.
https://doi.org/10.1016/j.scs.2023.104801
Asabere P, Sekyere F, Ayambire P, Ofosu WK. Optimal capacitor bank placement and sizing using particle swarm optimization for power loss minimization in distribution network. J Eng Res. 2024.
https://doi.org/10.1016/j.jer.2024.03.007
Roldán-Blay C, Escrivá-Escrivá G, Roldán-Porta C, Dasí-Crespo D. Optimal sizing and design of renewable power plants in rural microgrids using multi-objective particle swarm optimization and branch and bound methods. Energy. 2023;284:129318.
https://doi.org/10.1016/j.energy.2023.129318
Ajayi O, Heymann R. Day-ahead combined economic and emission dispatch with spinning reserve consideration using moth swarm algorithm for a data centre load. Heliyon. 2021;7(9):e08054.
https://doi.org/10.1016/j.heliyon.2021.e08054
Mukherjee A, Mukherjee V. Solution of optimal power flow using chaotic krill herd algorithm. Chaos Solitons Fract. 2015;78:10-21.
https://doi.org/10.1016/j.chaos.2015.06.020
Mahdad B, Srairi K. Security constrained optimal power flow solution using new adaptive partitioning flower pollination algorithm. Appl Soft Comput. 2016;46:501-22.
https://doi.org/10.1016/j.asoc.2016.05.027
Liu J, Hou Y, Li Y, Zhou H. Advanced strategies on update mechanism of tree-seed algorithm for function optimization and engineering design problems. Exp Syst Appl. 2024;236:121312.
https://doi.org/10.1016/j.eswa.2023.121312
El Sehiemy RA, Selim F, Bentouati B, Abido MA. A novel multi-objective hybrid particle swarm and salp optimization algorithm for technical-economical-environmental operation in power systems. Energy. 2020;193:116817.
https://doi.org/10.1016/j.energy.2019.116817
Mei NS, Sulaiman MH, Mustaffa Z, Daniyal H. Optimal reactive power dispatch solution by loss minimization using moth-flame optimization technique. Appl Soft Comput J. 2017;59:210-22.
https://doi.org/10.1016/j.asoc.2017.05.057
Taher MA, Kamel S, Jurado F, Ebeed M. An improved moth-flame optimization algorithm for solving optimal power flow problem. Int Trans Electr Energy Syst. 2019;29(3):1-28.
https://doi.org/10.1002/etep.2743
Bouchekara H. Solution of the optimal power flow problem considering security constraints using an improved chaotic electromagnetic field optimization algorithm. Neural Comput Appl. 2020;32(7):2683-703.
https://doi.org/10.1007/s00521-019-04298-3
Chen G, Qian J, Zhang Z, Li S. Application of modified pigeon-inspired optimization algorithm and constraint-objective sorting rule on multi-objective optimal power flow problem. Appl Soft Comput J. 2020;92:106321.
https://doi.org/10.1016/j.asoc.2020.106321
Coello Coello CA. Use of a self-adaptive penalty approach for engineering optimization problems. Comput Ind. 2000;41(2):113-27.
https://doi.org/10.1016/S0166-3615(99)00046-9
Ghasemi M, Ghavidel S, Ghanbarian MM, Massrur HR, Gharibzadeh M. Application of imperialist competitive algorithm with its modified techniques for multi-objective optimal power flow problem: A comparative study. Inf Sci (NY). 2014;281:225-47.
https://doi.org/10.1016/j.ins.2014.05.040
Rashedi E, Nezamabadi-pour H, Saryazdi S. GSA: A gravitational search algorithm. Inf Sci (NY). 2009;179(13):2232-48.
https://doi.org/10.1016/j.ins.2009.03.004
Chen G, Yi X, Zhang Z, Wang H. Applications of multi-objective dimension-based firefly algorithm to optimize the power losses, emission, and cost in power systems. Appl Soft Comput J. 2018;68:322-42.
https://doi.org/10.1016/j.asoc.2018.04.006
Shabanpour-Haghighi A, Seifi AR, Niknam T. A modified teaching-learning based optimization for multi-objective optimal power flow problem. Energy Convers Manag. 2014;77:597-607.
https://doi.org/10.1016/j.enconman.2013.09.028
Sivasubramani S, Swarup KS. Multi-objective harmony search algorithm for optimal power flow problem. Int J Electr Power Energy Syst. 2011;33(3):745-52.
https://doi.org/10.1016/j.ijepes.2010.12.031
Webster B, Bernhard PJ. A local search optimization algorithm based on natural principles of gravitation. Proc Int Conf Inf Knowl Eng. 2003;1:255-61.
Erol OK, Eksin I. A new optimization method: Big Bang-Big Crunch. Adv Eng Softw. 2006;37(2):106-11.
https://doi.org/10.1016/j.advengsoft.2005.04.005
Neshat M, Sepidnam G, Sargolzaei M, Toosi AN. Artificial fish swarm algorithm: a survey of the state-of-the-art, hybridization, combinatorial and indicative applications. Artif Intell Rev. 2014;42(4):965-97.
https://doi.org/10.1007/s10462-012-9342-2
Bonabeau E, Theraulaz G. Swarm intelligence: from natural to artificial systems. 1st ed. Santa Fe Institute Studies on the Sciences of Complexity. Oxford University Press; 1999. 320 p.
Alatas B. ACROA: Artificial chemical reaction optimization algorithm for global optimization. Expert Syst Appl. 2011;38(10):13170-80.
https://doi.org/10.1016/j.eswa.2011.04.126
Hatamlou A. Black hole: A new heuristic optimization approach for data clustering. Inf Sci (NY). 2013;222:175-84.
https://doi.org/10.1016/j.ins.2012.08.023
Caer C, Le Roux X, Do VK, Marris-Morini D, Izard N, Vivien L, et al. Dispersion engineering of wide slot photonic crystal waveguides by Bragg-like corrugation of the slot. IEEE Photon Technol Lett. 2011;23(18):1298-300.
https://doi.org/10.1109/LPT.2011.2158996
Du H, Wu X, Zhuang J. Small-world optimization algorithm for function optimization. Lect Notes Comput Sci. 2006;4222:264-73.
https://doi.org/10.1007/11881223_33
Hosseini HS. Principal components analysis by the galaxy-based search algorithm: a novel metaheuristic for continuous optimisation. Int J Comput Sci Eng. 2011;6(1/2):132.
https://doi.org/10.1504/ijcse.2011.041221
Mirjalili S, Lewis A. S-shaped versus V-shaped transfer functions for binary Particle Swarm Optimization. Swarm Evol Comput. 2013;9:1-14.
https://doi.org/10.1016/j.swevo.2012.09.002
Paul K, Hati D. A novel hybrid Harris hawk optimization and sine cosine algorithm based home energy management system for residential buildings. Build Serv Eng Res Technol. 2023;44(4):459-80.
https://doi.org/10.1177/01436244231170387
Paul K. Multi-objective risk-based optimal power system operation with renewable energy resources and battery energy storage system: A novel Hybrid Modified Grey Wolf Optimization–Sine Cosine Algorithm approach. Trans Instit Meas Control. 2022.
https://doi.org/10.1177/01423312221079962
Paul K, Kumar N. Cuckoo search algorithm for congestion alleviation with incorporation of wind farm. Int J Electr Comput Eng (IJECE). 2018;8(6):4871-9.
https://doi.org/10.11591/ijece.v8i6.pp4871-4879
Paul K, Shekher V, Kumar N, Kumar D, Kumar M. Influence of wind energy source on congestion management in power system transmission network: a novel modified whale optimization approach. Process Integr Optimiz Sustain. 2022;6:1-17.
https://doi.org/10.1007/s41660-022-00271-1
Pandya SB, Kalita K, Čep R, Jangir P, Chohan JS, Abualigah L. Multi-objective snow ablation optimization algorithm: an elementary vision for security-constrained optimal power flow problem incorporating wind energy source with FACTS devices. Int J Comput Intell Syst. 2024;17(1):33.
https://doi.org/10.1007/s44196-024-00415
Agrawal S, Pandya S, Jangir P, Kalita K, Chakraborty S. A multi-objective thermal exchange optimization model for solving optimal power flow problems in hybrid power systems. Dec Anal J. 2023;8:100299.
https://doi.org/10.1016/j.dajour.2023.100299
Kalita K, Ramesh JVN, Cepova L, Pandya SB, Jangir P, Abualigah L. Multi-objective exponential distribution optimizer (MOEDO): a novel math-inspired multi-objective algorithm for global optimization and real-world engineering design problems. Sci Rep. 2024;14:1816.
https://doi.org/10.1038/s41598-024-52083-7
Pandya SB, Jangir P, Mahdal M, Kalita K, Chohan JS, Abualigah L. Optimizing brushless direct current motor design: An application of the multi-objective generalized normal distribution optimization. Heliyon. 2024;10(4):e26369.
Wang C, Ma L, Ma L, Lai JW, Zhao J, Wang L, et al. Identification of influential users with cost minimization via an improved moth flame optimization. J Comput Sci. 2023;67:101955.
https://doi.org/10.1016/j.jocs.2023.101955
Yin L, Cai Z. Multimodal hierarchical distributed multi-objective moth intelligence algorithm for economic dispatch of power systems. J Clean Prod. 2024;434:140130.
https://doi.org/10.1016/j.jclepro.2023.140130
Suhail Shaikh M, Raj S, Babu R, Kumar S, Sagrolikar K. A hybrid moth–flame algorithm with particle swarm optimization with application in power transmission and distribution. Dec Anal J. 2023;6:100182.
https://doi.org/10.1016/j.dajour.2023.100182
Premkumar M, Hashim TJT, Ravichandran S, Ching Sin T, Chandran R, Alsoud AR, et al. Optimal operation and control of hybrid power systems with stochastic renewables and FACTS devices: An intelligent multi-objective optimization approach. Alex Eng J. 2024;93:90-113.
https://doi.org/10.1016/j.aej.2024.02.069
Jafar-Nowdeh A, Babanezhad M, Arabi-Nowdeh S, Naderipour A, Kamyab H, Abdul-Malek Z, et al. Meta-heuristic matrix moth–flame algorithm for optimal reconfiguration of distribution networks and placement of solar and wind renewable sources considering reliability. Environ Technol Innov. 2020;20:101118.
https://doi.org/10.1016/j.eti.2020.101118
Meng A, Zeng C, Wang P, Chen D, Zhou T, Zheng X, et al. A high-performance crisscross search based grey wolf optimizer for solving optimal power flow problem. Energy. 2021;225:120211.
https://doi.org/10.1016/j.energy.2021.120211
Muro C, Escobedo R, Spector L, Coppinger R. Wolf-pack (Canis lupus) hunting strategies emerge from simple rules in computational simulations. Behav Process. 2011;88:192-7.
Deng W, Shang S, Cai X, Zhao H, Song Y, Xu J. An improved differential evolution algorithm and its application in optimization problem. Soft Comput. 2021;25:5277-98.
Abd El-Mageed AA, Al-Hamadi A, Bakheet S, Abd El-Rahiem AH. Hybrid sparrow search-exponential distribution optimization with differential evolution for parameter prediction of solar photovoltaic models. Algorithms. 2024;17(1):26.
300-bus system (IEEE test case). Power Systems and Evolutionary Algorithms [Internet]. 2015 [cited 2021 Feb 11]. Available from: https://al-roomi.org/power-flow/300-bus-system.

Author information

Diego Morales, Andres Gutierrez, Lucia Navarro & Pablo Rios contributed to this work.

Authors and affiliations

Department of AI in Renewable Energy Systems, Faculty of Engineering, University of Lima, Lima, Peru
Diego Morales, Andres Gutierrez & Pablo Rios

Department of Smart Energy Analytics, Faculty of Engineering, Pontifical Catholic University of Peru, Lima, Peru
Lucia Navarro

Corresponding author

Correspondence to Diego Morales

Rights and permissions

Open Access The author(s) retain copyright. This article is licensed under the Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License. It may be shared and adapted for non-commercial purposes with appropriate attribution, an indication of changes, and distribution of adaptations under the same license. Third-party material may be subject to separate terms identified in its credit line. View the license at https://creativecommons.org/licenses/by-nc-sa/4.0/.

About this article

Cite this article

Vancouver
Morales D, Gutierrez A, Navarro L, Rios P. Multi-Objective Optimal Power Flow Using SF-MFO and Comparative Metaheuristic Algorithms. J Artif Intell Smart Energy Syst. 2024;3:38.
APA
Morales, D., Gutierrez, A., Navarro, L., & Rios, P. (2024). Multi-Objective Optimal Power Flow Using SF-MFO and Comparative Metaheuristic Algorithms. Journal of Artificial Intelligence in Smart Energy Systems, 3, 38.
Received
08 January 2023
Revised
15 March 2023
Accepted
31 March 2023
Published
15 June 2024
Version of record
15 June 2024

Share this article

Easily share this article with others using the link below:

Multi-Objective Optimal Power Flow Using SF-MFO and Comparative Metaheuristic Algorithms
Scan to access
this article

Ready to submit?
Start a new submission or continue a submission in progress:
Submission Portal Author Guidelines

Follow this journal
Get notified of new updates and articles.